EasyManua.ls Logo

ABB PCS100 UPS-I - 8 Operating PCS100 UPS-I; Starting, Stopping, and GDM Control

ABB PCS100 UPS-I
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
66 PCS100 UPS-I User Manual
8 OPERATING PCS100 UPS-I
8.1 Starting and Stopping PCS100 UPS-I
The primary method of starting and stopping the PCS100 UPS-I is via the Graphical Display Module (GDM) which
is mounted in the door of the master inverter enclosure. This is deemed Local Control. Start/Stop control of the
PCS100 UPS-I via the digital I/O terminals (Section 13.2) is deemed Remote Control.
8.1.1 GDM Control
The Start (I) / Stop (O) /Reset button in the Navigation & Control Panel allows GDM control of the PCS100 UPS-I.
When the PCS100 UPS-I is stopped (Bypass) a green Start (I) button will show, and when running (RUN) a red Stop
(O) button will show. Pressing the Start (I)/ Stop (O)/ Reset button followed by YES in the following confirmation
screen will cause that action to be taken. Figure 8-1: GDM Status Page shows the status page when the PCS100
UPS-I is running.
Start/Stop/Reset
Button
Figure 8-1: GDM Status Page
Note: If parameter A31 GDM Control Enable is set to False the Start/Stop/Reset button will not be displayed.

Table of Contents

Related product manuals