Temperature Alarms
The Pulsar Edge has several alarm thresholds that can be set based on temperature.
• High Temperature Alarm: The High Battery Thermal Alarm Threshold (thr) is the monitored battery temperature at
which above this threshold results in a High Battery Thermal alarm. This alarm threshold can be set from 30°C to
85°C and its severity is configurable. The alarm retires when the temperature drops to 10°C below the set
threshold. The factory default setting is 55°C with Power Minor severity.
• Very High Temperature Alarm: The Very High Battery Thermal Alarm Threshold is a second alarm threshold
available for high battery temperature. The monitored battery temperature at which above this threshold results in
a Very High Battery Thermal alarm. This alarm threshold can be set from 30°C to 85°C and its severity is
configurable. The alarm retires when the temperature drops to 10°C below the set threshold. The factory default
setting is TBD°C with Power Major severity.
• Low Temperature Alarm: The Low Battery Thermal Alarm Threshold is the monitored battery temperature at which
below this threshold results in a Low Battery Thermal alarm. This alarm threshold can be set from -40°C to 10°C and
its severity is configurable. The alarm retires when the temperature raises 10°C above the set threshold. The factory
default setting is TBD°C with Power Minor severity.
• Very Low Temperature Alarm: The Very Low Battery Thermal Alarm Threshold is a second alarm threshold available
for low battery temperature. The monitored battery temperature at which below this threshold will result in a Very Low
Battery Thermal alarm. This alarm threshold can be set from 40°C to 10°C and its severity is configurable. The alarm
retires when the temperature raises 10°C above the set threshold. The factory default setting is TBD°C with Power Major
severity.
Figure 26 Slope Thermal Compensation