The following describes the configuration parameters which may be Enabled/Disabled and configured
by the user. Refer to Appendix D for the ranges of values the parameters may take and their factory
default settings.
Temperature Alarms
The Pulsar Edge has several alarm thresholds that can be set based on temperature.
High Temperature Alarm: The High Battery Thermal Alarm Threshold (thr) is the monitored battery temperature at
which above this threshold results in a High Battery Thermal alarm. This alarm threshold can be set from 30°C to
85°C and its severity is configurable. The alarm retires when the temperature drops to 10°C below the set
threshold. The factory default setting is 55°C with Power Minor severity.
Very High Temperature Alarm: The Very High Battery Thermal Alarm Threshold is a second alarm threshold
available for high battery temperature. The monitored battery temperature at which above this threshold results in
a Very High Battery Thermal alarm. This alarm threshold can be set from 30°C to 85°C and its severity is
configurable. The alarm retires when the temperature drops to 10°C below the set threshold. The factory default
setting is TBD°C with Power Major severity.
Low Temperature Alarm: The Low Battery Thermal Alarm Threshold is the monitored battery temperature at which
below this threshold results in a Low Battery Thermal alarm. This alarm threshold can be set from -40°C to 10°C and
its severity is configurable. The alarm retires when the temperature raises 10°C above the set threshold. The factory
default setting is TBD°C with Power Minor severity.
Very Low Temperature Alarm: The Very Low Battery Thermal Alarm Threshold is a second alarm threshold available
for low battery temperature. The monitored battery temperature at which below this threshold will result in a Very Low
Battery Thermal alarm. This alarm threshold can be set from 40°C to 10°C and its severity is configurable. The alarm
retires when the temperature raises 10°C above the set threshold. The factory default setting is TBD°C with Power Major
severity.
Figure 26 Slope Thermal Compensation