EasyManua.ls Logo

ABB Pulsar Edge - Battery Recharge Current Limit; Battery Parameter Defaults; Table 5 Supported Battery Types

ABB Pulsar Edge
202 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 161
© Copyright 2021 ABB. All rights reserved.
Battery Recharge Current Limit
The battery recharge current limit feature enables the Pulsar Edge controller to limit the recharge
current flowing into a battery section during the charge cycle. The recharge current flowing into the
battery section can be limited to any value between 5A and 1000A.
Note that this feature will not have any impact on the current being delivered to the load. Further, there
will be no effect on the discharge current flowing from the battery strings to the load during an ac fail
condition. The controller will try and maintain the recharge current to within 10% of the set level.
Battery Parameter Defaults
The Pulsar Edge controller has been configured with battery specific defaults. These battery types are
shown in the top portion of Table 5. The generic Valve-Regulated Lead Acid battery is the default
battery type for this controller configuration. Battery models and their parameters can be added or
adjusted in the field.
M12V90FT 90
M12V105FT 104
M12V155FT 155
NCX-125 125
NCX-80 80
NSB110FT 111
NSB170FT 168
NSB60FT 60
SBS-145 148
SBS-170 170
TEL12-90 88
TEL12-105 100
XE60 59.3
12A100FT 96
12A150FT 145
12AVR145 145
12FAT130 127
12FAT155 155
12IR150/150LP 145
IR40EC 35
Flooded
Ni-Cd
Li-LMP 63
Li-ELiTE 63
Table 5 Supported Battery Types