Page 181
© Copyright 2021 ABB. All rights reserved.
Category Description Range Valve-Reg Flooded Li_ELiTE NiCd Li-LMP obj,attr
Voltage
Settings
Shutdown
58.50 58.50 58.50 58.50 58.50 GM1,FSD
57.00 57.00 57.00 57.00 57.00 HVA1,FTH
56.00 56.00 56.00 56.00 56.00 HFV1,FTH
54.48 52.08 54.48 54.40 54.48 GM1,FSP
51.00 50.00 53.00 51.00 51.00 BDA1,FTH
46.00 46.00 46.00 46.00 46.00 VLA1,THR
44.00 44.00 44.00 44.00 44.00 DC1,ROT
Battery
Disconnec
t
1=Enabled
0=Disabled
CN1,ENA
42.00 42.00 42.00 42.00 42.00 CN1,DTH
48.00 48.00 48.00 48.00 48.00 CN1,RTH
42.00 42.00 42.00 42.00 42.00
CN1,DTH
mode
46.00 46.00 46.00 46.00 46.00 CN1,DVX
CN1,DIN
300 300 300 300 300 CN1,DIX
24 24 24 24 24 DC1,CPS
Batteries
48.75V
42.00 42.00 42.00 42.00 42.00 BR1,CEV
1=Enabled
0=Disabled
BR1,CLE
50 50 25 25 25 BR1,CLT
BS1,TMD
1.7 1.7 1.7 2.0 1.7 BR1,SCV
75 75 75 75 75 BR1,TTH
55 55 55 55 85
BTHA1,TH
R
65 65 65 65 85
BTVH1,TH
R
-10 -10 -10 -10 -10
BTLA1,TH
R
-20 -20 -20 -20 -20
BTVL1,TH
R
Table 7 48V Battery Related Items