REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
3-279
D. Breaker failure protection settings – BreakerFailure
Summary of parameters:
Text Unit Default Min. Max. Step
CB commands
TRIP t1 B00000000
TRIP t1 L1 B00000000
TRIP t1 L2 B00000000
TRIP t1 L3 B00000000
TRIP t2 B00000000
REMOTE TRIP B00000000
RED TRIP L1 B00000000
RED TRIP L2 B00000000
RED TRIP L3 B00000000
EFP REM TRIP B00000000
EFP BUS TRIP B00000000
General parameters
ParSet4..1 P1 (Select)
I Setting IN 1.20 0.20 5.00 0.01
Delay t1 s 0.15 0.02 60.00 0.01
Delay t2 s 0.15 0.02 60.00 0.01
Delay tEFP s 0.04 0.02 60.00 0.01
t Drop Retrip s 0.05 0.02 60.00 0.01
t Drop BuTrip s 0.05 0.02 60.00 0.01
t Puls RemTrip s 0.05 0.02 60.00 0.01
t1 active on (Select)
t2 active on (Select)
RemTrip active on (Select)
EFP active on (Select)
Red active on (Select)
Start Ext act. on (Select)
RemTrip after t1 (Select)
NrOfPhases 3 1 3 2
CurrentInp
CT/VT-Addr
0
Block BFP BinaryAddr F