ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-280
Text Unit Default Min. Max. Step
Start L1 BinaryAddr F
Start L2 BinaryAddr F
Start L3 BinaryAddr F
Start L1L2L3 BinaryAddr F
External Start BinaryAddr F
CB Off BinaryAddr F
CB On BinaryAddr F
Ext Trip t2 BinaryAddr F
Ext Trip EFP BinaryAddr F
Trip t1 SignalAddr ER
Trip t1 L1 SignalAddr ER
Trip t1 L2 SignalAddr ER
Trip t1 L3 SignalAddr ER
Trip t2 SignalAddr ER
Remote Trip SignalAddr ER
Red Trip L1 SignalAddr ER
Red Trip L2 SignalAddr ER
Red Trip L3 SignalAddr ER
EFP Rem Trip SignalAddr ER
EFP Bus Trip SignalAddr ER
Retrip t1 SignalAddr ER
Uncon Trip t1 SignalAddr ER
Ext Trip t1 SignalAddr ER
Backup Trip t2 SignalAddr ER
Uncon Trip t2 SignalAddr ER
Explanation of parameters:
TRIP t1
defines the tripping channel activated by the function’s trip-
ping output TRIP t1 (matrix tripping logic). This output is acti-
vated for a ‘Retrip’, ‘External Trip Initiate’ or ‘Unconditional
Trip’.