REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
3-345
Example:
n = 10
a = 9
b = 2 (i.e. 9 to 16 signals)
p = 20 ms
s 44.5ms 20
12)292(
)22)110((65535
t
rec
=´
´+´
´+-
=
It follows that for the given number of channels and power sys-
tem frequency, the capacity is sufficient for 10 events of 540 ms
duration each.
File PLOT.TXT
PLOT.TXT for WinEVE, REVAL (programs for evaluating distur-
bance recorder data) and INTERFAC (data conversion program
for running disturbance data on the test set XS92b).
General remarks
The programs (WinEVE, REVAL and INTERFAC) need the file
PLOT.TXT to be able to process the disturbance recorder data.
For INTERFAC, all disturbance recorder data RExxxx.xxx must
start with the letters RE.