ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-346
Example PLOT.TXT
Hardware configuration: A/D config: K9
Overcurrent: A1 (IN = 1A)
Overvoltage: U1 (UN = 100V)
******************************************************
N: 001
S: ABB_Relays_Ltd
D 0 : D 0 /CO: 1
D 1 : D 1 /CO: 2
D 2 : D 2 /CO: 3
D 3 : D 3 /CO: 4
D 4 : D 4 /CO: 5
D 5 : D 5 /CO: 6
D 6 : D 6 /CO: 7
D 7 : D 7 /CO: 8
D 8 : D 8 /CO: 9
D 9 : D 9 /CO: 10
D10 : D10 /CO: 11
D11 : D11 /CO: 12
D12 : D12 /CO: 13
D13 : D13 /CO: 14
D14 : D14 /CO: 15
D15 : D15 /CO: 1
U 0 : UR /CO: 2 /TR: 0.1981 /UN: UN
U 1 : US /CO: 4 /TR: 0.1981 /UN: UN
U 2 : UT /CO: 11 /TR: 0.1981 /UN: UN
I 3 : I0 /CO: 10 /TR: 10.83 /UN: IN
U 4 : U /CO: 7 /TR: 0.1981 /UN: UN
U 5 : U /CO: 13 /TR: 0.1981 /UN: UN
I 6 : IR /CO: 8 /TR: 10.83 /UN: IN
I 7 : IS /CO: 12 /TR: 10.83 /UN: IN
I 8 : IT /CO: 9 /TR: 10.83 /UN: IN
******************************************************
where:
N: station number: text
S: station name: text
Dnn binary channels: text (max. 8 char.)
Unn:, Inn: voltage channel, current channel: text (max. 8
char.)
/CO 1 to 15: number of the plot colour for WinEVE
(In the case of REVAL the plotting colour is de-
termined by the particular layout.)

Table of Contents