ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
5-42
The plug-in unit and channel number of the selected binary input
and a minus sign if it is inverted (e.g. -101) are indicated in the
parameter value column of the “Edit function parameters” win-
dow.
xyzz: x = non-inverted () or inverted (-) input
y = plug-in unit number (1...4)
zz = channel number (1...14).
Note:
To cancel the selection of a channel, select “Always FALSE” or
“Always TRUE ” in the “Select Binary Input” window.
Since channels can have several inputs assigned to them, chan-
nel with inputs already assigned to them are not especially indi-
cated in the channel selection window.
Output of another function
Every function input can be assigned either inverted or non-
inverted to output of another function. The respective function is
first selected in the “Output from function” window and then the
selection window with all the outputs of the corresponding func-
tion opens:
ÚSelect Binary InputÄÄÄ¿
³ ³
³ AlÚOutput from FunctionÄÄÄÄÄÄÄÄÄ¿
³ Al³ ³
³ Bi³ 0 [1234/00] System IO ³ect
³ Ou³ 0 [1234/00] OÉ 1 Current-DTÍÍÍÍÍÍÍÍÍÍÍÍ»
³ In³ 1 [1000/00] Cº º
³ In³ 2 [1000/00] VºÚÄÄÚÄÄ¿ º
³ In³ 3 [1000/00] Pº³01³02³ º
³ RE³ 4 [1000/00] Vº³X ³ ³ º
³ ³ 5 [1000/00] DºÀÄÄÀÄÄÙ º
ÀÄÄij 6 [1000/00] FºTrip º
³ RETURN º º
³ ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍͼ
ÀÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙ
Fig. 5.18 “Output from function” selection window
The fields in the selection window are designated as follows:
Top: 1...47 : Channel No.
Bottom: X : selected channel (<Ins> key)
I : selected channel inverted (<-> key).
The signal name is displayed in the lower part of the window for
the field currently selected.