REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
5-91
The next task is to edit the files ‘Station.cfg’ and ‘MMKShell.mnu’
in the configuration dialogue.
The following parameters are set in ‘Station.cfg’:
COMT : Communication parameters
TC57 = communication via interface at the front
SPA = communication via the SPA-BUS interface
MDM = communication via modem and SPA-BUS
interface
SRIO = direct communication via SRIO
RDM = communication via modem and SRIO.
BAUD : Baud rate.
TNR : Station telephone number (T...tone dialling,
P...impulse dialling)
MPAR : Modem initialisation parameters; in most cases the
default settings are satisfactory.
Select SAVE to confirm the parameter settings and update the file.
Fig. 5.65 Window for editing the station configuration
An entry for each device in the station has to be made in the file
‘MMKShell.mnu’. The actual entry varies according to Windows
version.