ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
5-134
· Level 5:
The next level, the Select module/part of unit window and the
data input window Setting Spacom slave address are reached
by pressing <Enter>. Now enter the SPA address for the de-
vice.
ÉÍ Select Organization Í» SMSBASE directory:
ºABB PoÉÍ Select Station Í» C:\SMS\BASE\
ÈÍÍÍÍÍͺABB BaÉÍ Select Object/Bay Í»
ÈÍÍÍÍÍͺNTP-2 ÉÍÍÍÍÍÍÍÍÍÍÍÍÍ Select Unit ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»a directory:
ÈÍÍÍÍÍͺREC31ÉÍÍÍÍÍÍÍÍ Select Module/Part of Unit ÍÍÍÍÍÍÍÍÍ»
ÈÍÍÍÍͺREC316 REC316 Control & Protection Terminalº
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍͼ
Organiz: ABB Power Automation Ltd
Station: ABB Baden
Obj/Bay: NTP-2 REC316 45
Unit: REC316 C Control & Protection Terminal
C=Create communication parameters S=Show transducer file
E=Edit A=Add D=Delete ESC=previous level ENTER=select
· Entering the address.
ÉÍ Select Organization Í» SMSBASE directory:
ºABB PoÉÍ Select Station Í» C:\SMS\BASE\
ÈÍÍÍÍÍͺABB BaÉÍ Select Object/Bay Í»
ÈÍÍÍÍÍͺNTP-2 ÉÍÍÍÍÍÍÍÍÍÍÍÍÍ Select Unit ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»a directory:
ÈÍÍÍÍÍͺREC31ÉÍÍÍÍÍÍÍÍ Select Module/Part of Unit ÍÍÍÍÍÍÍÍÍ»
ÈÍÍÍÍͺREC316 REC316 Control & Protection Terminalº
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍͼ
ÉÍ Setting SPACOM slave address ÍÍÍÍÍÍÍ»
º º
º The module address is: 001 º
º New address: 045 º
º º
Organiz: ABB Power Automation Ltd ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍͼ
Station: ABB Baden
Obj/Bay: NTP-2 REC316 45
Unit: REC316 C Control & Protection Terminal
Mod/Part: REC316 REC316 Control & Protection Terminal
C=Create communication parameters S=Show transducer file
E=Edit A=Add D=Delete ESC=previous level ENTER=select
If your wish to add further stations, return to the corresponding
level. For example, to insert another device, repeat all steps from
level 3.