Features Compact design
Perfectly matched for the REG216/
REG316*4
Provides protection of the whole stator
winding including the neutral point
Continuous supervision of the injection
voltage and the primary earthing system
Suitable for two separate earthing points
within the protected zone
Continuous self-supervision of the injection
signal with respect to amplitude and fre-
quency
Auxiliary DC power supply from station bat-
tery from 36 to 312 V DC
Applicable for all commonly used earthing-
and excitation-systems for generators
Continuous supervision of the insulation
resistance and calculation of the earth fault
resistance
The principle is based on the well-known
offset method, using injection of a low
frequency signal
Suitable for updating existing plants
Insensitive to external disturbances
Application The unit is applied for the protection of gen-
erators in block configuration for earth faults
on the generator side. For the implementation
of the 100% stator and rotor earth fault
protection using a REG216/316*4, an injec-
tion unit REX010 and the injection trans-
former REX011 are required. This injection
equipment can be applied to all common
generator earthing- and excitation-systems.
The protection is active during all states of
the machine, standstill as well as run-up and
run-down
Auxiliary unit for REG216/316*4
for 100% stator and rotor earth
fault protection
REX010/011
1MRB520123-Ben
Issued: June 2002
Changed since: November 1999
Data subject to change without notice