EasyManua.ls Logo

ABB REG316 4 Series - Page 674

ABB REG316 4 Series
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Auxiliary unit for REG216/316*4 for 100%
stator and rotor earth fault protection
ABB Switzerland Ltd
Utility Automation
REX010/011
1MRB520123-Ben
Page 2
Design General
The earth fault protection is based on the in-
jection of a coded signal. The resulting offset
voltage is utilized to calculate the earth resis-
tance (R
f
).
The injection signal is produced in the injec-
tion unit REX010 and applied to the genera-
tor through the transformer unit REX011. For
the coupling to the protected unit resistors
(R
E,
R
P
) are used. For the rotor earth fault
protection two capacitors are required in
addition.
The measurement signals for earth fault pro-
tection are processed by the REG216 or the
REG316*4 respectively.
The equipment described protects 100% of
the generator stator winding. Two indepen-
dent protection functions are applied: one for
95% and one, using a different algorithm, for
100% of the stator winding. The 100% func-
tion is calculating the earth resistance and the
95% function is measuring the neutral voltage
displacement of the generator.
a) The 100% function protects 35% of the
stator windings from the neutral point
for R
f = 0
and I
0max
= 15 A
b) The 95% function (U>) protects 95% of
the generator stator winding from the
terminals. This results in an overlap
(redundancy) of the two protection func-
tions as seen in Fig. 1.
The 100% function increases in sensitivity
with increasing earth fault resistance and
decreasing earth fault current.
Fig. 1
At standstill the full stator winding (100%) is
protected by the 100% function as seen in
Fig. 2. At the same time the entire excitation
winding is protected for earth faults. Because
of the excellent rejection of external interfer-
ences, the REX010/011 can be applied to all
types of excitation systems including thyris-
tor type.
Fig. 2
Hardware The protection equipment consists of the fol-
lowing units (Figures 4 – 8):
REG216/316*4: Numerical generator protection
REX010: Injection unit
REX011: Injection transformer unit
with auxiliary contactor
In addition the following components are
required:
- Earthing resistors in the generator neu-
tral point (R
ES
, R
PS
) and in the excita-
tion circuit (R
Er
, R
Pr
)
- Coupling capacitors in the excitation
circuit of the rotor
- Voltage transformers
The injection unit (REX010) together with
the injection transformer (REX011) produces
three coded square wave signals (Uis, Uir,
Ui) with a frequency f
N
/4. These square wave
signals are injected into the protected object
via the coupling components. The three
square waves have different amplitudes: Uis
(Injection signal for the stator), Uir (Injection
signal for the rotor) and Ui (reference signal
for the REG216/316*4). The injection unit
REX010 is connected to the station battery
and the injection signal voltage is generated
either by the battery or by an internal DC/DC
converter.
95% Stator earth fault protection
Overlap
100%
function Rf = 0
Stator earth fault
Rf > 0
N
eutral point
Terminal
Winding
Running machine
100% Stator earth fault function

Table of Contents

Related product manuals