ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-32
9.6.22. MinReactance 6
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R Delay s 00.50 0.20 60.00 0.01
14S10 R XA-Setting UN/IN -2.00 -5.00 00.00 0.01
14S11 R XB-Setting UN/IN -0.50 -2.50 +2.50 0.01
14S12 R NrOfPhases 001 1 3 1
14S13 R Angle deg 000 -180 180 005
14S14 R MaxMin <Select> MIN -1 1 2
MIN -1
MAX 1
Measured variables
Address Access Text Dec.
14V1 R UN/IN 3
Tripping levels
Address Access Text Dec.
14Q1 R UN/IN 3
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Start Set V155 4 14I2
14E4 Ditto Reset V155 8