REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-33
9.6.23. NPS-DT 7
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R Delay s 01.00 0.50 60.0 0.01
14S10 R I2-Setting IN 00.20 0.02 0.50 0.01
Measured variables
Address Access Text Dec.
14V1 R IN 3
Tripping levels
Address Access Text Dec.
14Q1 R IN 3
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Start Set V155 4 14I2
14E4 Ditto Reset V155 8