ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-34
9.6.24. NPS-Inv 11
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R k1-Setting s 10.00 5.00 60.00 0.10
14S10 R k2-Setting I2/IB 0.05 0.02 0.20 0.01
14S11 R t-min s 010.0 1.0 120. 0 0.1
14S12 R t-max s 1000 500 2000 1
14S13 R t-Reset s 0030 5 2000 1
14S14 R IB-Setting IN 1.00 0.50 2.50 0.01
Measured variables
Address Access Text Dec.
14V1 R IN 3
Tripping levels
Address Access Text Dec.
14Q1 R IN 3
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Start Set V155 4 14I20
14E4 Ditto Reset V155 8

Table of Contents