REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-35
9.6.25. Voltage 12
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R Delay s 02.00 0.02 60.00 0.01
14S10 R U-Setting UN 1.200 0.010 2.000 0.002
14S11 R MaxMin <Select> MAX (1ph) -3 3 2
MIN (3ph) -3
MIN (1ph) -1
MAX (1ph) 1
MAX (3ph) 3
14S12 R NrOfPhases 001 1 3 1
Measured variables
Address Access Text Dec.
14V1 R UN 3
Tripping levels
Address Access Text Dec.
14Q1 R UN 3
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Start Set V155 4 14I2
14E4 Ditto Reset V155 8