EasyManua.ls Logo

ABB REG316 4 Series - Page 730

ABB REG316 4 Series
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-42
9.6.32. Diff-Gen 23
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R g-Setting IN 0.10 0.10 0.50 0.05
14S10 R v-Setting 0.25 0.25 0.50 0.25
Measured variables
Address Access Text Dec.
14V1 R IN (Id-R) 2
14V2 R IN (Id-S) 2
14V3 R IN (Id-T) 2
Tripping levels
Address Access Text Dec.
14Q1 R IN (Id-R) 2
14Q2 R IN (Id-S) 2
14Q3 R IN (Id-T) 2
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip-R Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Trip-S Set V155 4 14I2
14E4 Ditto Reset V155 8
14E5 Trip-T Set V155 16 14I3
14E6 Ditto Reset V155 32
14E7 Trip Set V155 64 14I4
14E8 Ditto Reset V155 128

Table of Contents