REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-43
9.6.33. Distance 24
Basic channel No.: 14
Summary of parameters:
The starter and measurement settings (in columns Min., Max.
and Step) with the unit 'ohms/phase' have to be divided by 10 for
relays with a rated current of 5 A.
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP CB R 00000000B
14S6 R TRIP CB S 00000000B
14S7 R TRIP CB T 00000000B
14S9 R X (1)
W/ph
000.00 -300 300 0.01
14S10 R R (1)
W/ph
000.00 -300 300 0.01
14S11 R RR (1)
W/ph
000.00 -300 300 0.01
14S12 R RRE (1)
W/ph
000.00 -300 300 0.01
14S13 R k0 (1) 1 001.00 0 8 0.01
14S14 R k0Ang(1) deg 000.00 -180 90 0.01
14S15 R Delay(1) s 000.000 0 10 0.001
14S16 R X (2)
W/ph
000.00 -300 300 0.01
14S17 R R (2)
W/ph
000.00 -300 300 0.01
14S18 R RR (2)
W/ph
000.00 -300 300 0.01
14S19 R RRE (2)
W/ph
000.00 -300 300 0.01
14S20 R k0 (2) 1 001.00 0 8 0.01
14S21 R k0Ang(2) deg 000.00 -180 90 0.01
14S22 R Delay(2) s 000.00 0 10 0.01
14S23 R X (3)
W/ph
000.00 -300 300 0.01
14S24 R R (3)
W/ph
000.00 -300 300 0.01
14S25 R RR (3)
W/ph
000.00 -300 300 0.01
14S26 R RRE (3)
W/ph
000.00 -300 300 0.01
14S27 R k0 (3) 1 001.00 0 8 0.01
14S28 R k0Ang(3) deg 000.00 -180 90 0.01
14S29 R Delay(3) s 000.00 0 10 0.01

Table of Contents