EasyManua.ls Logo

ABB REG316 4 Series - Page 732

ABB REG316 4 Series
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-44
Address Access Text Unit Default Min. Max. Step
14S30 R X (4/OR)
W/ph
000.00 -300 300 0.01
14S31 R R (4/OR)
W/ph
000.00 -300 300 0.01
14S32 R RR (4/OR)
W/ph
000.00 -300 300 0.01
14S33 R RRE (4/OR)
W/ph
000.00 -300 300 0.01
14S34 R k0 (4/OR) 1 001.00 0 8 0.01
14S35 R
k0Ang(4/OR)
deg 000.00 -180 90 0.01
14S36 R Delay(4/OR) s 000.00 0 10 0.01
14S37 R X (BACK)
W/ph
000.00 -300 0 0.01
14S38 R R (BACK)
W/ph
000.00 -300 0 0.01
14S39 R RR (BACK)
W/ph
000.00 -300 0 0.01
14S40 R RRE (BACK)
W/ph
000.00 -300 0 0.01
14S41 R StartMode <Select> I> 2 6 2
UZ 4
OC 6
14S42 R
PhasSelMode
<Select>
solid ground
081
Solid ground 0
RTS(R) cycl 1
TRS(T) cycl 2
RTS acycl 3
RST acycl 4
TSR acycl 5
TRS acycl 6
SRT acycl 7
STR acycl 8
14S43 R ComMode <Select> off 0 5 1
off 0
PUTT Nondir
1
PUTT Fward 2
PUTT OR2 3
POTT 4
BLOCK OR 5