REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-69
9.6.45. Voltage-Bal 41
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R V-Unbalance UN 0.20 0.10 0.50 0.05
14S10 R Delay s 0.04 0.00 1.00 0.01
14S11 R t-Reset s 1.50 0.10 2.00 0.01
14S12 R NrOfPhases 003 1 3 2
Measured variables
Address Access Text Dec.
14V1 R UN (Ud-1) 2
14V2 R UN (Ud-2) 2
14V3 R UN (Ud-3) 2
Tripping levels
Address Access Text Dec.
14Q1 R UN (Ud-1) 2
14Q2 R UN (Ud-2) 2
14Q3 R UN (Ud-3) 2
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Start Set V155 4 14I2
14E4 Ditto Reset V155 8
14E5 Trip-Line1 Set V155 16 14I3
14E6 Ditto Reset V155 32
14E7 Trip-Line2 Set V155 64 14I4
14E8 Ditto Reset V155 28