ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-70
9.6.46. U/f-Inv 47
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R V/f-Setting UN/fN 01.10 1.05 1.20 0.01
14S10 R t-min min 0.20 0.01 2.00 0.01
14S11 R t-max min 60.0 5.0 100.0 0.1
14S12 R t-Reset min 60.0 0.2 100.0 0.1
14S13 R t[V/f=1.05] min 70.00 00.01 100.00 0.01
14S14 R t[V/f=1.10] min 70.00 00.01 100.00 0.01
14S15 R t[V/f=1.15] min 06.00 00.01 100.00 0.01
14S16 R t[V/f=1.20] min 01.000 00.001 30.000 0.001
14S17 R t[V/f=1.25] min 00.480 00.001 30.000 0.001
14S18 R t[V/f=1.30] min 00.300 00.001 30.000 0.001
14S19 R t[V/f=1.35] min 00.220 00.001 30.000 0.001
14S20 R t[V/f=1.40] min 00.170 00.001 30.000 0.001
14S21 R t[V/f=1.45] min 00.140 00.001 30.000 0.001
14S22 R t[V/f=1.50] min 00.140 00.001 30.000 0.001
14S23 R UB-Setting UN 01.00 0.80 1.20 0.01
Measured variables
Address Access Text Dec.
14V1 R UN/fN 2
14V2 R Hz 2