EasyManua.ls Logo

ABB REG316 4 Series - Page 758

ABB REG316 4 Series
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-70
9.6.46. U/f-Inv 47
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R V/f-Setting UN/fN 01.10 1.05 1.20 0.01
14S10 R t-min min 0.20 0.01 2.00 0.01
14S11 R t-max min 60.0 5.0 100.0 0.1
14S12 R t-Reset min 60.0 0.2 100.0 0.1
14S13 R t[V/f=1.05] min 70.00 00.01 100.00 0.01
14S14 R t[V/f=1.10] min 70.00 00.01 100.00 0.01
14S15 R t[V/f=1.15] min 06.00 00.01 100.00 0.01
14S16 R t[V/f=1.20] min 01.000 00.001 30.000 0.001
14S17 R t[V/f=1.25] min 00.480 00.001 30.000 0.001
14S18 R t[V/f=1.30] min 00.300 00.001 30.000 0.001
14S19 R t[V/f=1.35] min 00.220 00.001 30.000 0.001
14S20 R t[V/f=1.40] min 00.170 00.001 30.000 0.001
14S21 R t[V/f=1.45] min 00.140 00.001 30.000 0.001
14S22 R t[V/f=1.50] min 00.140 00.001 30.000 0.001
14S23 R UB-Setting UN 01.00 0.80 1.20 0.01
Measured variables
Address Access Text Dec.
14V1 R UN/fN 2
14V2 R Hz 2

Table of Contents