2.3.2  Switchgear functions
2.3.2.1  CTRL.Cxxxxx1 Circuit breaker - CB object and failure protection (1)
Table 7: CTRL.Cxxxxx1 Circuit breaker - CB object and failure protection (1)
IEC 61850 name SA name Description Values
CTRL.CBCILO1      
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.CBCSWI1      
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.CBXCBR1      
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.2  CTRL.DCXSWI1 Disconnector control (1)
Table 8: CTRL.DCXSWI1 Disconnector control (1)
IEC 61850 name
SA name Description Values
CTRL.DCCILO1      
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI1      
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI1      
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.3  CTRL.DCXSWI2 Disconnector control (2)
Table 9: CTRL.DCXSWI2 Disconnector control (2)
IEC 61850 name
SA name Description Values
CTRL.DCCILO2      
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI2      
.Pos.stSeld SELECTED CB selected 1=Selected
Table continues on next page
1MRS757807 B Section 2
DNP3 data mappings
Remote Monitoring and Control REC615 19
Point List Manual