Section 2  DNP3 data mappings
2.1  Overview
This document describes the DNP3 data points and structures available in the IED.
The data points are unmapped as a default on the DNP3 level. The point lists
describe a superset of all DNP3 data available through the standard configuration/s
including the optional functionalities.
The point tables show all the available DNP3 data points in the IEDs. The data
objects in the point tables are listed based on the AFL and data object IEC 61850
names.
As a default, the class assignments are Class 0 and Class 1 for binary inputs and
Class 0 and Class 2 for analog inputs. These assignments can be modified later.
Analog values are provided with default scalings. The scalings can be freely
modified by the user.
This list represents the superset of DNP3 points. The actual set of available points,
meaning the actual set of available applications, is determined by the IED's order
code.
2.2  Supported functions in REC615
Table 2: Supported functions
Function
IEC 61850 A B C
  CE01 CE02 CE03
Protection
1)2)
Three-phase non-directional overcurrent protection, low stage PHLPTOC
(1)
3)
(1)
3)
(1)
3)
Three-phase non-directional overcurrent protection, high stage PHHPTOC
(1)
3)
(1)
3)
(1)
3)
Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC 1 1 1
Three-phase directional overcurrent protection, low stage DPHLPDOC
(2)
3)
(2)
3)
(2)
3)
Three-phase directional overcurrent protection, high stage DPHHPDOC
(1)
3)
(1)
3)
(1)
3)
Non-directional earth-fault protection, low stage EFLPTOC
(1)
4)5)
(1)
4)5)
(1)
4)5)
Non-directional earth-fault protection, high stage EFHPTOC
(1)
4)5)
(1)
4)5)
(1)
4)5)
Non-directional earth-fault protection, instantaneous stage EFIPTOC
1
5)
1
5)
1
5)
Directional earth-fault protection, low stage DEFLPDEF
(2)
5)6)8)
(2)
5)6)8)
(2)
5)6)8)
Directional earth-fault protection, high stage DEFHPDEF
(1)
5)6)8)
(1)
5)6)8)
(1)
5)6)8)
Transient / intermittent earth-fault protection INTRPTEF
(1)
5)6)8)
(1)
5)6)8)
(1)
5)6)8)
Table continues on next page
1MRS757807 B Section 2
DNP3 data mappings
Remote Monitoring and Control REC615 15
Point List Manual