IEC 61850 name SA name Description Values
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI5
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI5
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.7 CTRL.DCXSWI6 Disconnector control (6)
Table 13: CTRL.DCXSWI6 Disconnector control (6)
IEC 61850 name SA name Description Values
CTRL.DCCILO6
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI6
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI6
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.8 CTRL.DCXSWI7 Disconnector control (7)
Table 14: CTRL.DCXSWI7 Disconnector control (7)
IEC 61850 name
SA name Description Values
CTRL.DCCILO7
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI7
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI7
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
1MRS757807 B Section 2
DNP3 data mappings
Remote Monitoring and Control REC615 21
Point List Manual