2.5.2.6 CTRL.DCXSWI5 Disconnector control (5)
Table 126: CTRL.DCXSWI5 Disconnector control (5)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
CTRL.DCXSWI5
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.5.2.7 CTRL.DCXSWI6 Disconnector control (6)
Table 127: CTRL.DCXSWI6 Disconnector control (6)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
CTRL.DCXSWI6
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.5.2.8 CTRL.DCXSWI7 Disconnector control (7)
Table 128: CTRL.DCXSWI7 Disconnector control (7)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
CTRL.DCXSWI7
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.5.2.9 CTRL.DCXSWI8 Disconnector control (8)
Table 129: CTRL.DCXSWI8 Disconnector control (8)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
CTRL.DCXSWI8
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.5.2.10 CTRL.ESSXSWI1 Earthing switch indication (1)
Table 130: CTRL.ESSXSWI1 Earthing switch indication (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
CTRL.ESSXSWI1
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
1MRS757807 B Section 2
DNP3 data mappings
Remote Monitoring and Control REC615 53
Point List Manual