2.5.2.16  CTRL.ESSXSWI7 Earthing switch indication (7)
Table 136: CTRL.ESSXSWI7 Earthing switch indication (7)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
CTRL.ESSXSWI7          
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.5.2.17  CTRL.ESSXSWI8 Earthing switch indication (8)
Table 137: CTRL.ESSXSWI8 Earthing switch indication (8)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
CTRL.ESSXSWI8          
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.5.3  Metering and measurand functions
2.5.3.1  LD0.CMMXU1 Phase currents (1)
Table 138: LD0.CMMXU1 Phase currents (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.CMMXU1   Phase-to-ground current      
.A.phsA.instCVal.mag I_INST_A -phsA magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.A.phsB.instCVal.mag I_INST_B -phsB magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.A.phsC.instCVal.mag I_INST_C -phsC magnitude 0.00..40.0 [xIn] R 0,40,0,4000
2.5.3.2  LD0.CSMSQI1 Sequence of currents (1)
Table 139: LD0.CSMSQI1 Sequence of currents (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.CSMSQI1   Sequence of currents      
.SeqA.c1.instCVal.mag I1_INST -Positive magnitude
0.00...40.0
[xIn] R 0,40,0,4000
.SeqA.c2.instCVal.mag I2_INST -Negative magnitude
0.00...40.0
[xIn] R 0,40,0,4000
.SeqA.c3.instCVal.mag I3_INST -Zero magnitude
0.00...40.0
[xIn] R 0,40,0,4000
1MRS757807 B Section 2
DNP3 data mappings
Remote Monitoring and Control REC615 55
Point List Manual