2.5.3.10  LD0.PEMMTR1 Power measurement and accumulated power values
(1)
Table 147: LD0.PEMMTR1 Power measurement and accumulated power values (1)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.PEMMTR1          
.DmdVArh.actVal ER_RV_ACM Forward reactive energy 0…1e10 R 0,1E10,0,1E10
.DmdWh.actVal EA_RV_ACM Forward active energy 0…1e10 R 0,1E10,0,1E10
.SupVArh.actVal ER_FWD_ACM Reverse reactive energy 0…1e10 R 0,1E10,0,1E10
.SupWh.actVal EA_FWD_ACM Reverse active energy 0…1e10 R 0,1E10,0,1E10
.TotPF.instMag PF_INST Average power factor -1…1 R -1,1,-100,100
.TotW.instMag P_INST Active power 0…999999 R 0,999999,0,999999
.TotVA.instMag S_INST Apparent power 0…999999 R 0,999999,0,999999
.TotVAr.instMag Q_INST Reactive power 0…999999 R 0,999999,0,999999
2.5.4  Protection functions
2.5.4.1  LD0.T1PTTR1 Thermal protection values (1)
Table 148: LD0.T1PTTR1 Thermal protection values (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.T1PTTR1          
.Tmp.mag - Object temperature -100…9999.9 R -100,9999.9.0,-1000,99999
.TmpRl.mag - Relative temperature 0…99.9 R 0,99.9,0,999
2.5.5  Protection-related functions
2.5.5.1  LD0.DARREC1 Autoreclosing values (1)
Table 149: LD0.DARREC1 Autoreclosing values (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.DARREC1          
.AutoRecSt.stVal STATUS Autorec. status -2…4 R -2,4,-2,4
.ShotPntr.stVal SHOT_PTR Shot pointer value 0…65535 R 0,65535,0,65535
2.5.5.2  LD0.SECRSYN1 Synchrocheck line and bus state (1)
Table 150: LD0.SECRSYN1 Synchrocheck line and bus state (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.SECRSYN1          
.EnSt.stVal - Energization state 0…4 R 0,4,0,4
Section 2 1MRS757807 B
DNP3 data mappings
58 Remote Monitoring and Control REC615
Point List Manual