IEC 61850 name SA name Description Values
CTRL.DCXSWI2
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.4 CTRL.DCXSWI3 Disconnector control (3)
Table 10: CTRL.DCXSWI3 Disconnector control (3)
IEC 61850 name SA name Description Values
CTRL.DCCILO3
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI3
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI3
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.5 CTRL.DCXSWI4 Disconnector control (4)
Table 11: CTRL.DCXSWI4 Disconnector control (4)
IEC 61850 name
SA name Description Values
CTRL.DCCILO4
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI4
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI4
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.6 CTRL.DCXSWI5 Disconnector control (5)
Table 12: CTRL.DCXSWI5 Disconnector control (5)
IEC 61850 name
SA name Description Values
CTRL.DCCILO5
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
Table continues on next page
Section 2 1MRS757807 B
DNP3 data mappings
20 Remote Monitoring and Control REC615
Point List Manual