2.3.6.39 LD0.TRPPTRC2 Global conditioning (2)
Table 69: LD0.TRPPTRC2 Global conditioning (2)
IEC 61850 name SA name Description Values
.Op.general - Operate input signal 1=Operate
.Tr.general - Trip output signal 1=Trip
2.3.6.40 LD0.LSHDPFRQ1 Load-shedding (1)
Table 70: LD0.LSHDPFRQ1 Load-shedding (1)
IEC 61850 name SA name Description Values
LD0.LSHDPTRC1
.Op.general OPERATE Stage operate 1=Operate
.Str.general START Stage start 1=Start
.RestLodOp.general RESTORE Restore the load 1=Restore
.RestLodStr.general ST_REST Start of restore 1=Start
2.3.6.41 LD0.LEDPTRC1 Global protection signals (1)
Table 71: LD0.LEDPTRC1 Global protection signals (1)
IEC 61850 name
SA name Description Values
LD0.LEDPTRC1 Global protection signals
.Op.general - -General Operate 1=Operate
.Op.phsA - -phsA Operate 1=Operate
.Op.phsB - -phsB Operate 1=Operate
.Op.phsC - -phsC Operate 1=Operate
.Str.general - -General Start 1=Start
.Str.phsA - -phsA Start 1=Start
.Str.phsB - -phsB Start 1=Start
.Str.phsC - -phsC Start 1=Start
2.3.7 Protection-related functions
2.3.7.1 LD0.DARREC1 Autorecloser (1)
Table 72: LD0.DARREC1 Autorecloser (1)
IEC 61850 name
SA name Description Values
LD0.DARREC1
.PrgRec1.stVal INPRO_1 AR 1st reclose 1=In progress
.PrgRec2.stVal INPRO_2 AR 2nd reclose 1=In progress
Table continues on next page