IEC 61850 name SA name Description Values
.PrgRec3.stVal INPRO_3 AR 3rd reclose 1=In progress
.PrgRec4.stVal INPRO_4 AR 4th reclose 1=In progress
.PrgRec5.stVal INPRO_5 AR 5th reclose 1=In progress
.PrgRec.stVal INPRO AR in progress 1=In progress
.CBManCls.stVal MAN_CB_CL CB manually closed 1=CB closed
.LO.stVal LOCKED Lockout status 1=Lockout
.UnsRec.stVal UNSUC_RECL Reclose fail status 1=Failed
.InBlkThm.stVal - Thermal block (status) 1=Block
.RdyRec.stVal READY Ready reclose status 1=Ready
.ActRec.stVal ACTIVE Active reclose status 1=Active
.PrgDsr.stVal DISCR_INPRO Discrimination time in p. 1=In progress
.PrgCutOut.stVal CUTOUT_INPRO Cutout time in progress 1=In progress
.FrqOpAlm.stVal FRQ_OP_ALM Frequent operation alarm 1=Alarm
.RclTmStr.stVal - Reclaim time started 1=Started
.ProCrd.stVal - Protection coordination 1=In progress
.Op.general CLOSE_CB Operate (close XCBR) 1=Close CB
.OpOpn.general OPEN_CB Operate (open XCBR) 1=Open CB
.UnsCBCls.stVal UNSUC_CB CB closing failed 1=Failed
.WtMstr.stVal CMD_WAIT Master signal to follower 1=Signal
2.3.7.2  LD0.SECRSYN1 Synchrocheck (1)
Table 73: LD0.SECRSYN1 Synchrocheck (1)
IEC 61850 name
SA name Description Values
LD0.SECRSYN1      
.SynPrg.stVal SYNC_INPRO Synch in progress 1=In progress
.FailCmd.stVal CMD_FAIL_AL CB close request failed 1=Failed
.FailSyn.stVal CL_FAIL_AL CB close command failed 1=Failed
2.3.7.3  LD0.SEQRFUF1 Fuse failure protection (1)
Table 74: LD0.SEQRFUF1 Fuse failure protection (1)
IEC 61850 name
SA name Description Values
LD0.SEQRFUF1      
.Str.general FUSEF_U General start 1=Start
.Str3Ph.general FUSEF_3PH Three-phase start 1=Start
Section 2 1MRS757807 B
DNP3 data mappings
36 Remote Monitoring and Control REC615
Point List Manual