2.4.1 System functions
2.4.1.1 LD0.DNPGGIO1 Parameter setting group control (1)
Table 96: LD0.DNPGGIO1 Parameter setting group control (1)
IEC 61850 name SA name Description Type
LD0.DNPGGIO1
.ActSG1.ctlVal - Setting group 1 On
.ActSG2.ctlVal - Setting group 2 On
.ActSG3.ctlVal - Setting group 3 On
.ActSG4.ctlVal - Setting group 4 On
.ActSG5.ctlVal - Setting group 5 On
.ActSG6.ctlVal - Setting group 6 On
2.4.1.2 LD0.LLN0/LPHD1 Reset indications and LEDs, reset device (1)
Table 97: LD0.LLN0/LPHD1 Reset indications and LEDs, reset device (1)
IEC 61850 name SA name Description Type
LD0.LLN0
.LEDRs1.Oper.ctlVal - Reset indications and LEDs On
.LEDRs2.Oper.ctlVal - Reset alarm LEDs On
LD0.LPHD1
.RsDev.Oper.ctlVal - Reset device On
2.4.2 Switchgear functions
2.4.2.1 CTRL.CBCSWI1 Circuit breaker control (1)
Table 98: CTRL.CBCSWI1 Circuit breaker control (1)
IEC 61850 name
SA name Description Type
CTRL.CBCSWI1
.Pos.Oper.ctlVal - Circuit breaker control On/Off
2.4.2.2 CTRL.DCXSWI1 Disconnector control (1)
Table 99: CTRL.DCXSWI1 Disconnector control (1)
IEC 61850 name
SA name Description Type
CTRL.DCCSWI1
.Pos.Oper.ctlVal - Disconnector control On/Off
Section 2 1MRS757807 B
DNP3 data mappings
44 Remote Monitoring and Control REC615
Point List Manual

Table of Contents

Other manuals for ABB Relion REC615

Related product manuals