EasyManua.ls Logo

ABB Relion REC615 - Section 4: Using the HMI; Using the local HMI; Logging in

ABB Relion REC615
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3.9.3 LD0.XGGIO120 Physical I/O
Table 93: LD0.XGGIO120 Physical I/O
IEC 61850 name SA name Description Values
LD0.XGGIO120
.Ind1.stVal - X120-Input 1 1/0=ON/OFF
.Ind2.stVal - X120-Input 2 1/0=ON/OFF
.Ind3.stVal - X120-Input 3 1/0=ON/OFF
.Ind4.stVal - X120-Input 4 1/0=ON/OFF
2.3.10 Automation functions
2.3.10.1 LD0.ATSABTC1 Automatic transfer switch (1)
Table 94: LD0.ATSABTC1 Automatic transfer switch (1)
IEC 61850 name SA name Description Values
LD0.ATSABTC1
.OpOpn1.general OPEN_CB1 CB open cmd for bus 1 1=Open
.OpCls1.general CLOSE_CB1 CB close cmd for bus 1 1=Close
.OpOpn2.general OPEN_CB2 CB open cmd for bus 2 1=Open
.OpCls2.general CLOSE_CB2 CB close cmd for bus 2 1=Close
.TrnBlkAlm.stVal BLKD_AL ATS blocked alarm 1=Alarm
.PrgAuto.stVal INPRO ATS in progress 1=In progress
2.4 Binary outputs
Table 95: Explanations of the binary output table columns
Column name
Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Type Output type. Some outputs can only be controlled with value “On”. Writing “Off” to
these points does not affect the function of the output. See the DNP3 control relay
output block parameters.
1MRS757807 B Section 2
DNP3 data mappings
Remote Monitoring and Control REC615 43
Point List Manual

Table of Contents

Other manuals for ABB Relion REC615

Related product manuals