2.3.6.31 LD0.PHPTOV3 Phase overvoltage protection (3)
Table 61: LD0.PHPTOV3 Phase overvoltage protection (3)
IEC 61850 name SA name Description Values
LD0.PHPTOV3
.Op.general OPERATE Stage operate 1=Operate
.Str.general START Stage start 1=Start
2.3.6.32 LD0.PSPTUV1 Positive-sequence undervoltage protection (1)
Table 62: LD0.PSPTUV1 Positive-sequence undervoltage protection (1)
IEC 61850 name SA name Description Values
LD0.PSPTUV1
.Op.general OPERATE Stage operate 1=Operate
.Str.general START Stage start 1=Start
2.3.6.33 LD0.NSPTOV1 Negative-sequence overvoltage protection (1)
Table 63: LD0.NSPTOV1 Negative-sequence overvoltage protection (1)
IEC 61850 name
SA name Description Values
LD0.NSPTOV1
.Op.general OPERATE Stage operate 1=Operate
.Str.general START Stage start 1=Start
2.3.6.34 LD0.FRPFRQ1 Frequency protection (1)
Table 64: LD0.FRPFRQ1 Frequency protection (1)
IEC 61850 name
SA name Description Values
LD0.FRPTRC1
.Str.general START Stage start 1=Start
LD0.FRPTOF1 Overfrequency
.Op.general OPR_OFRQ -Operate 1=Operate
LD0.FRPTUF1 Underfrequency
.Op.general OPR_UFRQ -Operate 1=Operate
LD0.FRPFRC1 Frequency gradient
.Op.general OPR_FRG -Operate 1=Operate
1MRS757807 B Section 2
DNP3 data mappings
Remote Monitoring and Control REC615 33
Point List Manual