2.5 Analog inputs
Table 116: Explanations of the analog input table columns
Column name Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Values The value range of the original IEC 61850 data. Scaling is needed to convert
floating point data into DNP3 integer values.
S Scaling type selected as default. Default “R” means ratio scaling. See the DNP3
communication protocol manual for details.
Arg 1, 2, 3, 4 Scaling argument values as default. When ratio scaling is selected, the four
values correspond to min value in, max value in, min value out, and max value
out. See the DNP3 communication protocol manual for details.
2.5.1 System functions
2.5.1.1 CTRL.LLN0 Local remote station off
Table 117: CTRL.LLN0 Local remote station off
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
CTRL.LLN0
.LocRem.stVal -
Off=0; Loc=1; Rem=2;
Station=3 0…3 R 0,3,0,3
2.5.1.2 LD0.DNPGGIO1 Active parameter setting group (1)
Table 118: LD0.DNPGGIO1 Active parameter setting group (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.DNPGGIO1
.ActSG.stVal - Active setting group 1…6 R 1,6,1,6
Section 2 1MRS757807 B
DNP3 data mappings
50 Remote Monitoring and Control REC615
Point List Manual