2.3.6.35 LD0.FRPFRQ2 Frequency protection (2)
Table 65: LD0.FRPFRQ2 Frequency protection (2)
IEC 61850 name SA name Description Values
LD0.FRPTRC2
.Str.general START Stage start 1=Start
LD0.FRPTOF2 Overfrequency
.Op.general OPR_OFRQ -Operate 1=Operate
LD0.FRPTUF2 Underfrequency
.Op.general OPR_UFRQ -Operate 1=Operate
LD0.FRPFRC2 Frequency gradient
.Op.general OPR_FRG -Operate 1=Operate
2.3.6.36 LD0.T1PTTR1 Thermal protection (1)
Table 66: LD0.T1PTTR1 Thermal protection (1)
IEC 61850 name SA name Description Values
LD0.T1PTTR1
.AlmThm.general ALARM Thermal alarm 1=Alarm
.Op.general OPERATE General operate 1=Operate
.Str.general START General start 1=Start
2.3.6.37 LD0.INRPHAR1 Three-phase inrush detection (1)
Table 67: LD0.INRPHAR1 Three-phase inrush detection (1)
IEC 61850 name
SA name Description Values
LD0.INRPHAR1
.Str.general - General start 1=Start
2.3.6.38 LD0.TRPPTRC1 Global conditioning (1)
Table 68: LD0.TRPPTRC1 Global conditioning (1)
IEC 61850 name
SA name Description Values
LD0.TRPPTRC1
.Op.general - Operate input signal 1=Operate
.Tr.general - Trip output signal 1=Trip