2.4.2.9 CTRL.DCXSWI8 Disconnector control (8)
Table 106: CTRL.DCXSWI8 Disconnector control (8)
IEC 61850 name SA name Description Type
CTRL.DCCSWI8
.Pos.Oper.ctlVal - Disconnector control On/Off
2.4.3 Sensors and monitoring functions
2.4.3.1 LD0.SSCBR1 Reset signals of CB condition monitoring (1)
Table 107: LD0.SSCBR1 Reset signals of CB condition monitoring (1)
IEC 61850 name SA name Description Type
LD0.SSCBR1
.RsAccAPwr.Oper.ctlVal RST_IPOW Reset accum. energy On
.RsCBWear.Oper.ctlVal RST_CB_WEAR Reset CB life and op. counter On
.RsSprChaTm.Oper.ctlVal RST_SPR_T Reset spring charge alarm On
.RsTrvTm.Oper.ctlVal RST_TRV_T Reset travel time alarm On
2.4.3.2 LD0.SSCBR2 Reset signals of CB condition monitoring (2)
Table 108: LD0.SSCBR2 Reset signals of CB condition monitoring (2)
IEC 61850 name
SA name Description Type
LD0.SSCBR2
.RsAccAPwr.Oper.ctlVal RST_IPOW Reset accum. energy On
.RsCBWear.Oper.ctlVal RST_CB_WEAR Reset CB life and op. counter On
.RsSprChaTm.Oper.ctlVal RST_SPR_T Reset spring charge alarm On
.RsTrvTm.Oper.ctlVal RST_TRV_T Reset travel time alarm On
2.4.4 Metering and measurand functions
2.4.4.1 LD0.PEMMXU1 Reset accumulated energy values (1)
Table 109: LD0.PEMMXU1 Reset accumulated energy values (1)
IEC 61850 name
SA name Description Type
LD0.PEMMXU1
.SupDmdRs.Oper.ctlVal RSTACM Reset accum. energy On
Section 2 1MRS757807 B
DNP3 data mappings
46 Remote Monitoring and Control REC615
Point List Manual