Function IEC 61850 A B C
CE01 CE02 CE03
Admittance based earth-fault protection EFPADM
(3)
5)7)8)
(3)
5)7)8)
(3)
5)7)8)
Wattmetric based earth-fault protection WPWDE
(3)
5)7)8)
(3)
5)7)8)
(3)
5)7)8)
Harmonics based earth-fault protection HAEFPTOC
(1)
5)7)
(1)
5)7)
(1)
5)7)
Negative-sequence overcurrent protection NSPTOC 2 2 2
Phase discontinuity protection PDNSPTOC 1 1 1
Residual overvoltage protection ROVPTOV
(1)
8)
(2)
9)10)
(1)
8)
Three-phase undervoltage protection PHPTUV (3)
(3)
11)
(3)
Three-phase overvoltage protection PHPTOV (3)
(3)
11)
(3)
Positive-sequence undervoltage protection PSPTUV (1) (1) (1)
Negative-sequence overvoltage protection NSPTOV (1) (1) (1)
Frequency protection FRPFRQ (2) (2) (2)
Three-phase thermal protection for feeders, cables and distribution transformers T1PTTR 1 1 1
Three-phase inrush detector INRPHAR 1 1 1
Master trip TRPPTRC 2 2 2
Multi-purpose protection MAPGAPC 6 6 6
Load shedding and restoration LSHDPFRQ (1) (1) (1)
Fault locator SCEFRFLO (1) (1) (1)
Power quality
Current total demand distortion CMHAI (1) (1) (1)
Voltage total harmonic distortion VMHAI (1) (1) (1)
Voltage variation PHQVVR (1) (1) (1)
Voltage unbalance VSQVUB (1) (1) (1)
Control
Circuit-breaker control
12)
CBXCBR 1 1 1
Disconnector control DCXSWI 8 8 8
Earthing switch indication ESSXSWI 8 8 8
Autoreclosing DARREC (1) (1) (1)
Synchronism and energizing check SECRSYN - 1 -
Automatic transfer switch ATSABTC (1) (1) (1)
Condition monitoring and supervision
Circuit-breaker condition monitoring SSCBR 2 2 2
Trip circuit supervision TCSSCBR 2 2 2
Fuse failure supervision SEQRFUF 1 1 1
Runtime counter for machines and devices MDSOPT 1 1 1
Voltage presence PHSVPR 1 2 1
Measurement
Disturbance recorder RDRE 1 1 1
Three-phase current measurement CMMXU 1 1 1
Table continues on next page
Section 2 1MRS757807 B
DNP3 data mappings
16 Remote Monitoring and Control REC615
Point List Manual