DNP3 device profile document
Sometimes
Configurable as: "Only when reporting event data", or "When reporting event data or multi-fragment messages"
Timeouts while waiting for:
Data link
confirm:
None Fixed at ____ Variable Configurable
Complete
appl. fragment:
None Fixed at ____ Variable Configurable
Application
confirm:
None Fixed at ____ Variable Configurable
Complete
appl.
response:
None Fixed at ____ Variable Configurable
Others: Select/Operate Arm timeout, configurable in DNP setting parameters. Regrdless of the select timeout in the HMI.
Need time interval, configurable
Unsolicited notification delay, configurable
Unsolicited response retry delay, configurable
Unsolicited offline Interval, configurable
Sends/Executes Control Operations:
WRITE binary
outputs
Never Always Sometimes Configurable
SELECT/
OPERATE
Never Always Sometimes Configurable
DIRECT
OPERATE
Never Always Sometimes Configurable
DIRECT
OPERATE -
NO ACK
Never Always Sometimes Configurable
Count > 1
(Count > 1 is
accepted but
ignored)
Never Always Sometimes Configurable
Pulse on Never Always Sometimes Configurable
Pulse off Never Always Sometimes Configurable
Latch on Never Always Sometimes Configurable
Latch off Never Always Sometimes Configurable
Queue Never Always Sometimes Configurable
Clear queue Never Always Sometimes Configurable
The circuit breaker control model is configurable for either direct or SBO mode in the circuit breaker settings. If the operation mode does
not match the CROB, the returned CROB status is hardware error (4). All other control points may be controlled by either direct or SBO
controls.
Reports binary input change events when no specific variation
requested:
Reports time-tagged binary input change events when no specific
variation requested:
Never Never
Only when time-tagged Binary input change with time
Only non-time-tagged Binary input change with relative time
Configurable to send one or the other Configurable
Sends unsolicited responses: Sends static data in unsolicited responses:
Never Never
Table continues on next page
Section 3 1MRS757807 B
DNP3 protocol implementation
64 Remote Monitoring and Control REC615
Point List Manual