EasyManuals Logo

ABB RET670 Commissioning Manual

ABB RET670
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #155 background imageLoading...
Page #155 background image
Now the signals TRIP1 and TRIP should be activated.
6. With reduced amplitude of the injected voltage to 0.8 VBase the current amplitude
and angle is changed via ZC + (ZA – ZC)/2 to a value corresponding to half IBase
and 180° between the injected current and voltage.
This is done with a speed so that the final impedance is reached after 1s. As the
injected voltage is lower than 0.92 VBase the PICKUP signal should be activated. In
addition to this the signal ZONE2 should be activated.
7. Set N2Limit to 1 and repeat step
6.
Now the signals TRIP2 and TRIP should be activated.
IED
B A
E
B
E
A
X’
d
X
T
Z
S
Zone 1 Zone 2
jX
R
ZB
ZA
Pole slip
impedance
movement
Zone 2
Zone 1
WarnAngle
TripAngle
f
ZC
ANSI07000099_2_en.vsd
ANSI07000099 V2 EN
Figure 38: Setting of the pole slip protection PSPPPAM (78)
1MRK 504 165-UUS - Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI 149
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals