EasyManua.ls Logo

ABB RET670 - Page 158

ABB RET670
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I = I(50 Hz) + I(49.5 Hz)
IEC10000141 V2 EN
Figure 40: Trajectory of the impedance Z(R, X) for the injected current with two
components: a 50 Hz component and a 49.5 Hz current component
The test of the out-of-step protection function requires the injection of the analog
quantities for a quite long time. The rating of the analogue channels is considered in order
to avoid any hardware damage. The test current is lower than the continuous permissive
overload current I
ovrl
of the protection current channels of the transformer module.
If the rated secondary current I
rs
of the analog channel is 1 A, then the maximum current
test I
ts
is
I I I A
ts ovrl rs
= × =4 4
EQUATION14041 V1 EN (Equation 1)
If the CT of the generator has ratio 9000/1 A, then in primary values
I I I
I
I
A
t ovrl p ovrl
rp
rs
= × = × =
,
4
9000
1
36000
EQUATION14042 V1 EN (Equation 2)
Reference is made to the numerical values of the example, explained in the “Setting
guidelines” of the Application Manual. A test current equal to 2.5 time the base current of
the generator is chosen; this choice is related to the selected test voltage that is applied
while testing the point SE and RE.
I I A
t Base
= × = × =2 5 2 5 8367 20918. .
EQUATION14043 V1 EN (Equation 3)
Section 11 1MRK 504 165-UUS -
Testing functionality by secondary injection
152 Transformer protection RET670 2.2 ANSI
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Related product manuals