EasyManua.ls Logo

ABB RET670 - Page 159

ABB RET670
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The parameter ReachZ1 defines the boundary between zone 1 and zone 2; it is expressed
in percent of the parameter ForwardX. If the setting of ReachZ1 = 12%, then
corresponding primary value of the reactance is
X
ReachZ ForwardX
ZBase
RZ 1
1
100 100
12
100
59 33
100
0 9522 0= × × = × × =
.
. .0068
EQUATION14044 V1 EN (Equation 4)
The calculation of the test voltage, that is related to ReachZ1, is based on the impedance
Z
RZ1
that has imaginary part X
RZ1
and real part R
RZ1
:
RRZ
achZ ForwardR
ZBase1
1
100 100
12
100
8 19
100
0 9522 0 0= × × = × × =
Re .
. . 009
EQUATION14045 V1 EN (Equation 5)
The magnitude of the impedance Z
RZ1
is:
2 2 2 2
1 1 1
0.009 0.068 0.069
RZ RZ RZ
Z R X= + = + = W
EQUATION14046 V1 EN (Equation 6)
Hence the reference voltage of the test of the boundary between zone 1 and zone 2 is
V Z I V
t RZ RZ t,
.
1 1
0 069 20918 1435= × = × =
EQUATION14047 V1 EN (Equation 7)
If the test voltage is lower than V
t,RZ1
(or in opposition), then the test is related to the zone
1; if the test voltage is higher than V
t,RZ1
, then the test is related to the zone 2.
Considering the resistances and reactances which are related to the settings (ForwardR,
ForwardX) and (ReverseR, ReverseX):
R
ForwardR
ZBase
FwdR
= × = × =
100
8 19
100
0 9522 0 078
.
. .
EQUATION14048 V1 EN (Equation 8)
X
ForwardX
ZBase
FwdX
= × = × =
100
59 33
100
0 9522 0 565
.
. .
EQUATION14049 V1 EN (Equation 9)
R
ReverseR
ZBase
RvsR
= × = × =
100
0 29
100
0 9522 0 003
.
. .
EQUATION14050 V1 EN (Equation 10)
X
ReverseR
ZBase
RvsX
= × = × =
100
29 6
100
0 9522 0 282
.
. .
EQUATION14051 V1 EN (Equation 11)
1MRK 504 165-UUS - Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI 153
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Related product manuals