The parameter ReachZ1 defines the boundary between zone 1 and zone 2; it is expressed
in percent of the parameter ForwardX. If the setting of ReachZ1 = 12%, then
corresponding primary value of the reactance is
X
ReachZ ForwardX
ZBase
RZ 1
1
100 100
12
100
59 33
100
0 9522 0= × × = × × =
.
. .0068Ω
EQUATION14044 V1 EN (Equation 4)
The calculation of the test voltage, that is related to ReachZ1, is based on the impedance
Z
RZ1
 that has imaginary part X
RZ1
 and real part R
RZ1
 :
RRZ
achZ ForwardR
ZBase1
1
100 100
12
100
8 19
100
0 9522 0 0= × × = × × =
Re .
. . 009Ω
EQUATION14045 V1 EN (Equation 5)
The magnitude of the impedance Z
RZ1
 is:
2 2 2 2
1 1 1
0.009 0.068 0.069 
RZ RZ RZ
Z R X= + = + = W
EQUATION14046 V1 EN (Equation 6)
Hence the reference voltage of the test of the boundary between zone 1 and zone 2 is
V Z I V
t RZ RZ t,
.
1 1
0 069 20918 1435= × = × =
EQUATION14047 V1 EN (Equation 7)
If the test voltage is lower than V
t,RZ1
 (or in opposition), then the test is related to the zone
1; if the test voltage is higher than V
t,RZ1
, then the test is related to the zone 2.
Considering the resistances and reactances which are related to the settings (ForwardR,
ForwardX) and (ReverseR, ReverseX):
R
ForwardR
ZBase
FwdR
= × = × =
100
8 19
100
0 9522 0 078
.
. . Ω
EQUATION14048 V1 EN (Equation 8)
X
ForwardX
ZBase
FwdX
= × = × =
100
59 33
100
0 9522 0 565
.
. . Ω
EQUATION14049 V1 EN (Equation 9)
R
ReverseR
ZBase
RvsR
= × = × =
100
0 29
100
0 9522 0 003
.
. . Ω
EQUATION14050 V1 EN (Equation 10)
X
ReverseR
ZBase
RvsX
= × = × =
100
29 6
100
0 9522 0 282
.
. . Ω
EQUATION14051 V1 EN (Equation 11)
1MRK 504 165-UUS - Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI 153
Commissioning manual