ScreenMaster RVG200
Paperless recorder 7 Configuration
92 OI/RVG200-EN
Engineering range * Select the display characteristics of the input.
Low
High
Units
**
Specify the display range and units of the engineering value
corresponding to the electrical high and low values, within the limits
defined in Table 7.3.
THC / RTD type
°C °F
Minimum Maximum Minimum Maximum
B –18 1800 0 3270
E –100 900 –140 1650
J –100 900 –140 1650
K –100 1300 –140 2350
L –100 900 –140 1650
N –200 1300 –325 2350
R&S –18 1700 0 3090
T –250 300 –400 570
Pt100 –200 600 –325 1100
Power 5/2
–99999 to +999999
Power 3/2
Square Root
Custom Linearizer 1
Custom Linearizer 2
Linear
Table 7.3 Limits of engineering ranges
* If this parameter is changed, internally-recorded data files are recreated and unarchived data is lost.
** Due to the display resolution, if more than 2 channels are assigned to a group, engineering units featuring
a superscript 3 character (for example, m
3
) may not be displayed correctly in the Chart views.