EBTH TEMPERATURE TRANSMITTER
CALIBRATION
B - 6
Bench Calibration
This procedure applies to EBTH Transmitters configured for either
ANALOG or DIGITAL. Any difference between the two are noted in
the Comments column.
Key Display Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select BENCH CALIB with the down arrow key.
Enter the low and high calibration voltages.
Enter the low and high calibration resistances.
Apply 0.00 mV to the transmitter. A message
appears that indicates a stabilization time.
NOTE: Refer to the EBTH instruction for detailed wir-
ing diagrams of this procedure.
CALI-
BRATE
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→ YES
ENTER
CALIBRATION
D-TO-A ADJUST
→ BENCH CALIB.
ENTER
LOW CALIB
n.nnn mV
HIGH CALIB
n.nnn mV
ENTER
LOW CALIB RES
n.nn Ω
HIGH CALIB RES
nnn.nn Ω
ENTER
APPLY
0.00 mV
AT 3(+), 4(-)
THEN HIT ENTER
WAITING FOR
CALIBRATION