EasyManua.ls Logo

ABB STT04 - Special Feature Key Functions; Fix Set Point;Cancel Fix Set Point; PID Parameters

ABB STT04
285 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SMART POSITIONER
SPECIAL FEATURE KEY FUNCTIONS
A - 10
SPECIAL FEATURE KEY FUNCTIONS
The special feature key selections available for the positioner vary
from the other supported devices. The unique selections pertaining
only to the positioner, are as follows:
Fix set point/cancel fix set point.
PID parameters.
Reset Totals.
Fix Set Point/Cancel Fix Set Point
This function locks the position demand set point at a user specified
value. This set point value is maintained by the positioner until it is
canceled using CANCEL FIX SET.
Key Display Comments
CLEAR
ID TAGNAME
READY
Key Display Comments
Select FIX SET POINT.
If CANCEL FIX SET is selected, press and
the fix set point is canceled and the READY screen
appears.
Use the number key pad to input the desired fix set
point value.
The set point remains at a fixed value until CANCEL
FIX SET is selected.
SPECIAL
FEATURE
FIX SET POINT
CANCEL FIX SET
PID PARAMETERS
STANDARD CONFIG
ENTER
ENTER
FIX SET POINT TO:
nnn.nn%
ENTER
ID TAGNAME
READY

Table of Contents

Related product manuals