AS800 PRESSURE TRANSMITTER
CALIBRATION
P - 8
METER VALUE ADJUSTMENT
Use this function to adjust the four to 20 milliampere output of the field
device using values from an external current meter. This method is
only valid for HART devices.
Use the arrow keys to adjust the 20 mA signal.
Key Display Comments
ENTER
ADJUST TO 20 mA
THEN HIT ENTER
ENTER
ID TAGNAME
READY
Key Display Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select D-TO-A ADJUST.
Select METER VALUE ENTRY.
CALI-
BRATE
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
YES
ENTER
CALIBRATION
D-TO-A ADJUST
BENCH CALIB.
ENTER
D/A CAL USING
UPDOWN ARROW KEYS
METER VALUE ENTRY