TB82 TRANSMITTER
CREATE/MODIFY CONFIGURATION
N - 3
Enter a day and press . Enter a month and
press . Enter a year.
This date can represent the creation date of the con-
figuration, the date the device or element was
installed, or some other significant date.
Select Linear.
The OUTPUT TYPE screen does not appear when
the transmitter type is TB82 CONC.
NOTE: Remote communications do not support the
function generator feature for the TB82. Function
generator output points must be specified locally at
the device.
Enter a value between 0 and 100. Damping is used
to smooth out a noisy signal. Use a low value for a
clean signal and a higher number for noisy signals.
Default setting is 0.5 seconds.
The DAMPING screen does not appear when the
transmitter type is TB82 CONC.
Input lower range value (4 mA) using the arrow keys,
then press . Input the upper range value
(20 mA).
The range values screen does not appear when the
transmitter type is TB82 CONC.
Select a temperature compensation type.
This screen appears for TB82 pH.
NOTE: AUTO SOL. (ADV) is only available for TB82
transmitters operating in advance mode.
Enter a temperature.
This screen appears for TB82 pH and only if MAN-
UAL is the temperature compensation type.
Select YES.
Key Display Comments
ENTER
DATE:
DAY: nn
MONTH: nn
YEAR: nnnn
ENTER
ENTER
ENTER
OUTPUT TYPE:
→ LINEAR
FUNC GENERATOR
ENTER
DAMPING:
(0 - 100 sec)
ENTER
LOWER RANGE VAL
nn.nn UNITS
UPPER RANGE VAL
nn.nn UNITS
ENTER
ENTER
TEMP COMP TYPE
→ MANUAL
AUTOMATIC
AUTO SOL. (ADV)
ENTER
ENTER
TEMPERATURE:
nn.nn UNITS
ENTER
STORE THIS
CONFIGURATION?
NO
→ YES