EasyManua.ls Logo

Airtec RO Plus l - Page 104

Default Icon
135 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
104
11. Troubleshooting
Nozzles dripping
Fault
code: Cause Solution
101
1. Air in system after service or rst startup.
2. If it is only a few nozzles it the zone that has a problem, it is
typically the nozzle. If it is several in same zone, see code 102.
1. Problem should eliminate itself after few hours
2. Replace the nozzle if the problem Is only with a few, or move to 102.
102
1. Non return valve is leaking or blocked:
a. Blocked valve cause the pressure to be relief through the
nozzle, so it spits water each time it stops.
b. Leaking valve causes air in system, and it makes the nozzles
spits or spray uneven at startup.
2. Non return valve is installed incorrect causing the function to
be opposite.
1. Check if the relief valve releases water when a zone is stopping, and
that it stops running after a few sec. Check one zone at the time. If
not replace it.
2. Check the ow direction on the non return valve, all zones, is from
system against drain, look at the “arrow” turn the valve if incorrectly
installed.
103
1. Solenoid valve unable to open correct, causing lack of water
and pressure.
2. Solenoid valve not closing to the zone, causing water leak with
a low ow to the zone/drain.
3. Solenoid valve relief port blocked.
4. Solenoid valve relief port leaking during operation.
1. Stop all other zones, run only the faulty zone to check if it open
correct. Replace Plunger kit, or valve if not
2. Stop all zones. Start them one at the time. When you start the zone
with a fault, the drain ow would stop. If not replace the entire valve.
3. Remove the non return valve to see if the valve can relief now. Is
it can, remove the blockade, or replace non return valve. If it still
cannot relief, replace valve.
4. Replace plunger kit. If that’s not enough, replace valve.
104
1. Defect / blocked lters may cause pass-through which lead to
no ltration, and possible blockade of nozzles
2. Dirt inside hoses from incorrect installation - not sealing hose
ends during installation, leading dirt to ow with the water
during rst startup. Particles bigger than nozzle orice will
block the nozzles.
3. Treated water with conductivity < 5 µS will in extreme cases
make the water act “static” so it sticks to all metal surface,
causing water dripping from the atomizer.
1. Check if the lter is colored on the inside (lter center), replace lters,
and ush hoses proper, before replacing nozzles.
2. Flush the hoses and replace defected nozzles.
3. Adjust atomizer away from metal parts and add nozzle extenders.
• If Adjustment is not enough, control of micro siemens level > 5 µS
is necessary.
OK
Replace
Defect
Change lter more often
201218

Table of Contents