Overload protection.
Cable from HydroSens to atomizers.
Recommendation:
System data is from installations done under minimum conditions as illustrated below, or better.
The single installation corrections, and reductions has to be done if installation is done in a way where temperature, numbers of cables installations type are aecting the
machine installation.
Fuse size 10 A
Cable XLPE 90° 1,5mm²
Reduction factor < 5 power circuit / multicore cables 0,77 * Iz Single layer installation type E or F
Circuit load < 8 Amp
Cable installation distance Minimum 1 x cable diameter
Temperature correction factor 0,87 * Iz At < 45°C
Cable current value 18,5 Amp Installation type A2 or better.
4. Datasheet
1. I load ≤ I fuse ≤ I cable.
2. 8A ≤ 10A ≤ ( 18,5 * 0,77 * 0,87 ) = 8A ≤ 10A ≤ 12,38 A
Short circuit protection.
See CE label, technical data sheet and electric diagram for:
Fn Rated frequency
Ic Short-circuit current
Icc Rated conditional short-circuit current
Icp Prospective short-circuit current
InA Rated current
Inc Rated current single circuits
Un Rated voltage