EasyManua.ls Logo

Airtec RO Plus l - Page 47

Default Icon
135 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
47
6. Startup & Commissioning
Adjust by-pass, continued:
• Enable ”ON/OFF AHU 1” in terminal row connection.
• to goto ”Adjust By-pass” screen.
• Loosen the by-pass.
•
to start the system, if it dosn’t start to reset alarms.
•
to edit.
•
or until ”Yes”.
• Adjust the by-pass slowly CW until setpoint is reached, tile limit 30 sec.
•
or until ”No” or wait until it automaticly returns to ”No”.
•
to exit edit.
• Lock by-pass position.
Adjust By-Pass
Adjust By-Pass Yes
Pressure, Bar XX.X
Adjust By-Pass locknut
Flow test:
•
or to goto ”Flow Test & Setup” screen.
•
to edit.
•
or until ”Test” is ”Duct 1.1.” for testing duct 1 valve 1.
Flow Test & Setup
Test Duct X.X Yes
Hysteresis, Hz XX.X
Inverter Freq, Hz XX.X
LowFlow Installed Yes
Alarm Delay, Sec. XX
Alarm On
• to goto ”No”.
•
or until ”Yes”, test time 1 min. when the test is done ”Yes” returns to ”No”, ow value is
automaticly stored.
•
If pump speed stay on max. speed during the hole ow test - check for leakage.
•
If the pump speed isn’t stable at the end of the ow test - run the test again.
• Run the ow test for all active AHU/ducts and valves.
• If LowFlow kit is installed, run ow test for zone ”LowFlow.
•
to exit edit.
•
Redo ow test as last thing before ending commessioning.
AHU startup, one AHU at
the time:
• Goto ”AHU Overview” screen.
• If running 0-100 % control signal ”0-100%.
- Get a control signal > 10 %, >1 V DC.
• If running Room control ”Room %RH”.
- Adjust ”Room %RH” setpoint > actual %RH.
• Enable ”ON/OFF AHU” for the actual AHU.
< AHU Overview >
°-1- °-2- °-3-
Step X X X
Control % XXX XXX XXX
Room %RH XXX XXX XXX
Setpoint XX XX XX
Duct %RH XXX XXX XXX
Setpoint XX XX XX
• Check:
- Leakage.
- Its the right AHU and valve spraying.
- Sensor location.
- Does it reach setpoint and step down.
• Leave AHU with nal setting.
• Repeat AHU check for next AHU.
• Check supply water pressure, and inverter amps with all AHU’s on step 7.
• Fill out AirtecCare checklist.
201218

Table of Contents